PVC Insulated Power Cable
Standard and Scope of Application
The products can be produced and provided according to Chinese
standard GB/T12706-2002(equivalent to IEC 60505). The factory can
also manufacture the products that are based on British
Standard(BS) and other standards. In addition, under the
requirement of customers we can design and manufacture the products
that have special performance. The products are used in fixed
laying on transmission and distribution electrical lines of 50 HZ
AC rated voltage up to 6 kV.
Specific Property for Using
1. The long-time permissible working temperature of cable
conductive core is not more than 70C.
2. During short circuit(max permanent time is not more than 5
seconds), the max temperature of cable conductor is not more than
165C.
3. The difference level of laying cable is not restricted. When
laying the cable, ambient temperature is not lower than 0C.
4. They have good chemical stability, and properties of acid
resistance, alkali resistance, salt resistance, oil resistance,
solvent resistance and flame resistance.
5. Light weight, good bending property and easy installation and
maintenance.
Technical Requirement
3.1 Type and Name
Type Name
VV VLV Copper(aluminum)Conductor, PVC insulated and Sheathed Power
Cable
VY VLY Copper(aluminum)Conductor, PVC insulated, PE Sheathed Power
Cable
VV22VLV22 Copper(aluminum)Conductor, PVC insulated, Steel-tape
Armoured, PVC Sheathed Power Cable
VV23VLV23 Copper(aluminum)Conductor, PVC insulated, Steel-tape
Armoured, PE Sheathed Power Cable
VV32VLV32 Copper(aluminum)Conductor, PVC insulated, Fine Steel-wire
Armoured, PVC Sheathed Power Cable
VV33VLV33 Copper(aluminum)Conductor, PVC insulated, PE Sheathed
Power Cable
VV42VLV42 Copper(aluminum)Conductor, PVC insulated, Thick
Steel-wire Armoured, PVC Sheathed Power Cable
VV43VLV43 Copper(aluminum)Conductor, PVC insulated, Thick
Steel-wire Armoured, PE Sheathed Power Cable
3.2 Nominal cross section of conductive core
(master core)1 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300
(3+1 neutral core)1.5 2.5 4 6 10 16 25 35 50 70 95 120 150
(3+2 neutral core)1.5 2.5 4 6 10 16 25 35 50 70 95 120 150
3.3 Nominal thickness of insulation
Nominal Cross
Sectrion (mm2)
Insulated
Thickness(mm)
Voltage(KV)
1 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630
800 1000
0.6/1 0.8 0.8 0.8 1 1 1 1 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4
2.6 2.8 2.8 2.8 3.0
3.6/6 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
3.4DC resistance of conductor
Nominal
Cross
Section
(mm2) at 20C, DC resistance is
Not more than (/km) Nominal
Cross
Section
(mm2) at 20C, DC resistance is
Not more than (/km) Nominal
Cross
Section
(mm2) at 20C, DC resistance is
Not more than (/km)
Copper Core Aluminum Core Copper Core Aluminum Core Copper Core
Aluminum Core
1.5 12.1 18.1 35 0.524 0.868 240 0.0754 0.125
2.5 7.41 12.1 50 0.387 0.641 300 0.0601 0.100
4 4.61 7.41 70 0.268 0.443 400 0.0470 0.0778
6 3.08 4.61 95 0.193 0.320 500 0.0366 0.0605
10 1.83 3.08 120 0.153 0.253 630 0.0283 0.0469
16 1.15 1.91 150 0.124 0.206 800 0.0221 0.0369
25 0.727 1.20 185 0.0991 0.164 1000 0.0176 0.0291
3.5 Insulation Resistance
Test item PVC insulated Cable XLPE insulated Power Cable
0.6/1KV 3.6/6KV
Volume resistivity (. Cm)
Min. At 20C
At top rated temperature min. 1013
1010 1014
1011 -
1012
Ki insulation resistivity constant(M. Km)
Min. At 20C
At top rated temperature min. 36.7
0.037 367
0.37 -
3.67
3.6 insulation resistance
UO/U(KV) Us(KV) T(min
0.6/1 3.5 5
3.6/6 12.5 5